NEWPORT ULTRA-MINIATURE
TEMPERATURE TRANSMITTERS
NEWPORT Ultra-Miniature temperature transmitters convert millivolt inputs from thermocouples or resistance from RTD’s into 4-20mA outputs. Transmitters are available in color-coded enclosures covering the four most popular thermocouple types (J, K, T and E) as well as three-wire 100 Ohm platinum RTD’s.
Featuring state-of-the-art integrated circuits and electronic design these ultra-compact transmitters have a diameter of only 35.6mm (1.40”) and are designed to fit in many compact thermowell protection heads such as the NEWPORT NB2.
Models TX93A and TX94A transmitters can
eliminate long runs of costly field wiring in a
variety of applications.
A stable 4 to 20 mA output signal is provided
proportional to the transmitters specific input type
and calibrated temperature range.
Adjustability of ±25% for zero and span is provided
to facilitate some rangeability.
The transmitted signal eliminates noise pickup,
voltage drops, multiple cold junction errors and
requires only a twisted pair of copper wire for loop
connections.
All models and ranges of these NEWPORT ultra-miniature transmitters are available with fully epoxy-potted electronics (specify -P option) providing the ultimate protection in extreme environments.
SPECIFICATIONS
Industrial
Thermocouple
Protection Head
Available
from NEWPORT
|
Output
Range:
4-20 mA dc
Zero and Span Adjustment Range:
±25%
Accuracy:
±0.1% of FS (includes effects of linearity, hysteresis
and repeatability)
Frequency Response:
3dB @ 3 Hz
Operating Temperature Range:
-25 to 85°C (-13 to 185°F)
Storage Temperature Range:
-65 to 125°C (-85 to 257°F)
Supply Voltage:
8-35 Vdc, 24V recommended
Max
Loop Resistance:
Dimensions: 35.6 mm Dia. x 23.6 mm H (1.40" x 0.93") height includes terminal strip
Weight: 15 g ( 0.53 oz.); 25 g (0.8 oz) if epoxy-potted.
RANGE
CODES
|
Range
|
TX93A |
TX94A |
|
J
|
K
|
T
|
E
|
RTD
|
| -40 to 49°C (-40 to 120°F) |
J1 |
- |
- |
E1
|
1
|
| -18 to 93°C (0 to 200°F) |
J2 |
K2 |
T2 |
E2
|
2
|
| -18 to 149°C (0
to 300°F) |
J3 |
K3 |
T3 |
E3
|
3
|
| -18 to 260°C (0
to 500°F) |
J4 |
K4 |
T4 |
E4
|
4
|
| -18 to 399°C (0
to 750°F) |
J5 |
K5 |
T5 |
E5
|
5
|
| -18 to 538°C (0
to 1000°F) |
J6 |
K6 |
- |
E6
|
6
|
- Not
an available range
|
|
|
|
† All dollar amounts on this site are shown in US currency.
Note: (1) Thermocouple models, output proportional to mV output of thermocouple. Not linearized to temperature. (2) Non-isolated unit for use with ungrounded probes. (3) Each unit supplied with complete operator’s manual.
Ordering Example: (1) TX93A-J4 J4, type J, transmitter with -18 to 260°C (0 to 500°F) range = $85
|
|
 |
 |
 |
 |
 |
 |
 |
 |
 |
Part Number Builder |
 |
 |
 |
 |
 |
 |
|
|
|
Option Descriptions
|
|
(1)
|
Transmitter Type
|
| |
Select TX93A for Thermocouple transmitter TX94A for RTD transmitter
|
(2)
|
Sensor Type and Temperature Range
|
| |
Select J1 for J Thermocouple -40 to 49°C (-40 to 120°F) E1 for E Thermocouple -40 to 49°C (-40 to 120°F) J2 for J Thermocouple -18 to 93°C (0 to 200°F) K2 for K Thermocouple -18 to 93°C (0 to 200°F) T2 for T Thermocouple -18 to 93°C (0 to 200°F) E2 for E Thermocouple -18 to 93°C (0 to 200°F) J3 for J Thermocouple -18 to 149°C (0 to 300°F) K3 for K Thermocouple -18 to 149°C (0 to 300°F) T3 for T Thermocouple -18 to 149°C (0 to 300°F) E3 for E Thermocouple -18 to 149°C (0 to 300°F) J4 for J Thermocouple -18 to 260°C (0 to 500°F) K4 for K Thermocouple -18 to 260°C (0 to 500°F) T4 for T Thermocouple -18 to 260°C (0 to 500°F) E4 for E Thermocouple -18 to 260°C (0 to 500°F) J5 for J Thermocouple -18 to 399°C (0 to 750°F) K5 for K Thermocouple -18 to 399°C (0 to 750°F) E5 for E Thermocouple -18 to 399°C (0 to 750°F) J6 for J Thermocouple -18 to 538°C (0 to 1000°F) K6 for K Thermocouple -18 to 538°C (0 to 1000°F) E6 for E Thermocouple -18 to 538°C (0 to 1000°F) 1 for RTD -40 to 49°C (-40 to 120°F) 2 for RTD -18 to 93°C (0 to 200°F) 3 for RTD -18 to 149°C (0 to 300°F) 4 for RTD -18 to 260°C (0 to 500°F) 5 for RTD -18 to 399°C (0 to 750°F) 6 for RTD -18 to 538°C (0 to 1000°F)
|
(3)
|
Option
|
| |
Select Nothing(leave field blank) for no option -P for Fully Epoxy-Potted Electronics for extreme environments
|
| NOTE: All combinations may not be valid, check spec sheet for valid part numbers. |
| |
|
 |
 |
|
|
|
|
Keywords: Xmitter Transmitter Thermocouple Loop Power
|
Back to top |
|
|